Boiler Water Treatment Part 2 – Internal Treatment Objectives of Internal Water Treatment 1 – To control the level of total dissolved solids (TDS) within the boiler As water is boiled within the boiler and steam is produced, then the solids remain in the water and concentrate. Thus, over time the level of total dissolved solids (TDS) increases.
lexie@zozen.com > Get A Quote >As steam is evaporated the concentration of total dissolved solids (TDS) increases in the boiler water. If the TDS concentration is allowed to get too high then carryover of boiler water will occur. This carryover can cause serious damage to the steam and condensate systems through corrosion and deposition on heat transfer surfaces.
lexie@zozen.com > Get A Quote >TDS level - As the boiler water TDS increases, the steam bubbles become more stable, and are more reluctant to burst and separate. Corrective action against carryover. The following alternatives are open to the Engineering Manager to minimise foaming in the boiler: Operation - Smooth boiler operation is important. With a boiler operating under
lexie@zozen.com > Get A Quote >The TDS in the blowdown water – the higher the TDS, the lower the amount of blowdown; The average load level for the boiler (BHP / kW or lbs /kg. of steam per hour) As can be seen from the above, applications with high make-up levels, high TDS in the make-up water and extended operation at high load levels result in high levels of blowdown.
lexie@zozen.com > Get A Quote >Measuring TDS with the density method. TDS = 1.1 10 6 (ρ - 1) (1) where. TDS = Total Dissolved Solids (ppm) ρ = relative density of the boiler water at 15.5 o C. This is a manual method requiring measuring a cooled down sample with a very sensitive hydrometer. Measuring TDS with the conductivity method
lexie@zozen.com > Get A Quote >By installing an automatic TDS control system the average boiler water TDS can be maintained at a level almost equal to the maximum allowable TDS as shown in Figure 3.12.9; Evaluating savings by reducing blowdown rate. If a boiler is to supply a given amount of steam, the water blown down must be in addition to this amount.
lexie@zozen.com > Get A Quote >“blowdown” refers to the removal of boiler water in order to maintain an acceptable level of Total Dissolved Solids (TDS). Blowdown has an economic impact because the water that is removed has been heated from the inlet temperature to the steam saturation temperature and the energy used to heat this water, of course, comes from
lexie@zozen.com > Get A Quote >A level gauge and an operator are not enough for the optimal water level in a steaming boiler to be maintained. A level gauge indicates a lower-than-average water-surface level in a boiler shell because of such factors as: Steam-generation rate. Height of the gauge connection. TDS and chemicals. Size of the boiler shell. Boiler circulation.
lexie@zozen.com > Get A Quote >Incorrect level control can result in boiler lockouts or carryover of boiler water into the steam system. The LP20 / PA20 level probe and LC2650 control system is well matched for medium to large steam boiler installations with a varying steam demand. This control system is ideal for applications where close control of tank or boiler water